6" TFT colour VGA Handy Touch Panel Display DC power supply type VT3-V6HG

VT3-V6HG - 6" TFT colour VGA Handy Touch Panel Display DC power supply type

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

Software

  • CE Marking
  • CSA

Specifications

Model

VT3-V6HG

General specifications

Current consumption

380mA or less

Structure

IP65f equivalent dust proof, waterjet proof

Overvoltage category

I

Pollution degree

3

Power voltage

24 VDC ±10%

Noise resistance

1500 Vp-p pulse width 1 µs 50 ns (common mode, based on noise simulator)

Withstand voltage

1500 VAC 1 minute (between power terminal and housing)

Insulation resistance

50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing)

Vibration resistance

Intermittent vibration

Frequency: 5 to 9 Hz

Half amplitude:3.5 mm*1

Frequency: 9 to 150 Hz

Acceleration: 9.8 m/s2*1

Continuous vibration

Frequency: 5 to 9 Hz

Half amplitude:1.75 mm*1

Frequency: 9 to 150 Hz

Acceleration: 4.9 m/s2 *1

Ground

Class D grounding (Class 3 grouding).

Operating environment

Minimal amount of dust and corrosive gas present

Ambient operating temperature

0 to +50°C *2*3

Ambient operating humidity

35 to 85%RH (No condensation)*4*3

Ambient storage temperature

-10 to +60°C (No freezing)

Ambient storage humidity

35 to 85%RH (No condensation)*4*3

Drop

According to JIS B 3502 IEC61131-2 (1.3m)

Weight

Approx 1120 g*5

Performance specifications

Displaypanel

Display elements

TFT colour LCD

Display colour

32768 colours

Number of points displayed

W 640 × H 480 points

Active display area

W 132.5 × H 99.4 mm

Service life (normal temperature andhumidity)

Approx 50000 h

Backlightlamp

System

White LED (Not replaceable)

Life-span

Approx 50000 h

Touchswitch

Number of switches

80×60/screen

System

Analogue resistive membrane type

Operating force

0.98N or less

Life-span

1,000,000 times or more

Screen data internal memory

Memory capacity

12 MB (memory extension enabled)

Number of pages that can be registered

Up to 1024 pages

Number of screens that can be registered

Up to 1024 screens

Page No.: 0 to 8999, Global window No.: G000 to G999, Report screen P.00 to P.15

Data backup

Screen data

Flash ROM can be erased 100000 times.

Recording data

SRAM backup:lithium battery

Character font

Outline font, Bitmap font, Stroke font Windows font, IMAGE font, Small font

Calendar timer

Accuracy: ±40s/month (25°C), Backup:lithium battery (5 years above of service life at 25°C)

Communication function

PLC host link

KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota),
Koyo Electronics Industries, Yokogawa Electric, Toshiba, Toshiba Machine, Fanuc, GE Fanuc Automation, Rockwell (Allen Bradley), Siemens

Thermostat

Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO

Inverter

Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON

Servo amplifier

Mitsubishi Electric

Stepping motor

Orienltal Motor

Robot controller

IAI

Eco-power meter

Panasonic Electric Works

General-purpose communication

Based on specific commands

I/O specifications

Function switch (FSW1/FSW2/FSW5/FSW6)

Number of outputs

4 (FSW1, FSW2, FSW5, FSW6)

Common terminal

4 terminals/common (FSWC)

Output

MOSFET (N-ch; with overcurrent protection function)

Rated load

30 VDC 0.1 A

Leakage current (at OFF)

100 µA or less

Residual voltage (at ON)

1.0V or less

Durability

300,000 times or more

Enabling switch (EN1A/EN1B/EN2A/EN2B)

Rated voltage

30 VDC

Rated current

1 A (resistive load), 0.7 A (inductive load)

Contact method

2a contact

Durability

Mechanical

Position 1 -> 2 -> 1: 1,000,000 times or more, position 1 -> 2 -> 3 -> 1: 100,000 times or more

Electrical

100,000 times or more

Function

The following 3-position-operation is available: position 1: off (when not pressed), position 2: on (when pressed to the middle position), position 3: off (when pressed as far as possible). * When the position returns from position 3 (when pressed as far

RS-232C/422 communication (CN2A/CN2B)

Applied standard

Conforms to EIA RS-232C and RS-422

Synchronisation between the transmitter and receiver

Start-stop, full duplex

Communication distance

15m (RS-232C)/500m (RS-422)

Data length

7 or 8 bits

Parity

Even, odd, none

Communication speed

1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

Ethernet communication (CN3)

Compliance

IEEE802.3

Transmission speed

10 Mbps (10BASE-T),100 Mbps (100BASE-TX)

Transmission medium

STP or category 3 or higher UTP (10BASE-T), STP or category 5 or higher UTP (100BASE-TX)*6

Maximum cable length

100 m

Maximum number of connectable hubs

4 (10BASE-T),2 (100BASE-TX)

Maximum number of connections

PC application:*7 3,
FTP: 4

MegaLink/multi-link (A/B/G)

When connected through MegaLink

Applied standard

RS-485

Synchronisation between the transmitter and receiver

Start-stop, half duplex

Communication speed

19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps

Cable connection

Multi-drop (branching is not possible)

Maximum number of connectable units

15

Baud rate 19200

Maximum extension distance: 1,000 m

Baud rate 115200

Baud rate 0.5 M

Maximum extension distance: 500 m

Baud rate 1 M

Maximum extension distance: 200 m

Baud rate 2 M

Maximum extension distance: 100 m

When connected through VT multi-link

Applied standard

RS-485

Synchronisation between the transmitter and receiver

Start-stop, half duplex

Communication distance

Maximum extension distance: 500 m or less

Communication speed

19200, 115200, 0.5M, 1M bit/s

Baud rate 115200 or less

Maximum extension distance: 500 m

Baud rate 0.5 M

Maximum extension distance: 100 m

Baud rate 1 M

Maximum extension distance: 50 m

When connected through multi-link

Applied standard

RS-485

Synchronisation between the transmitter and receiver

Start-stop, half duplex

Communication distance

Maximum extension distance: 500 m or less

Communication speed

19200, 38400, 57600, 115200 bit/s

*1 Conforms to JIS B 3502, IEC61131-2
Number of sweeps: 10 times respectively in the X, Y, and Z directions (100 minutes)
*2 Please use the unit in the condition of the ambient temperature at 0 to 40°C when the back light power is set to “”.
*3 Use this product under the condition that if the ambient temperature exceeds 40°C, the absolute humidity is 40°C 85% RH or less.
*4 When the ambient temperature is higher than 40°C, please use it in the condition of an absolute humidity of 85%RH at 40°C.
*5 Excluding individual unit and cable.
*6 STP = shielded twisted pair cable, UTP = unshielded twisted pair cable
*7 PC application refers to VT STUDIO and DATA BUILDER.

Data Sheet (PDF) Other Models